The placement of a Third Party Product on this page is indicative only that the Third Party Product has been tested for interoperability with the DeltaV system. EMERSON PROCESS MANAGEMENT PROVIDES NO WARRANTY OF DESIGN, MATERIAL, WORKMANSHIP, PERFORMANCE, FITNESS, MERCHANTABILITY OR OTHERWISE IN CONNECTION WITH THIRD PARTY PRODUCTS. Warranties for Third Party Products may be obtained only from the applicable manufacturer.
Updated: April 30, 2010
Fieldbus Type A Cable Belden 3076F or Equivalent
| MTL-Relcom |
| Safe Area, Class I Division 2 and Zone 2: |
| |
FPS-I |
Redundant Fieldbus Power Supply With Terminator >>Additional Info: Relcom Application |
| |
FPS-2 |
Redundant Fieldbus Power Supply (Without Terminator) |
| |
FPS-DT |
Dual (2 Segment) Fieldbus Power Supply With Terminator |
| |
FPS-D |
Dual (2 Segment) Fieldbus Power Supply (Without Terminator) |
| |
8 Segment Redundant Power Supply (includes 2 F801 Power Modules (350 mA) with Carrier) |
| |
|
F890-P* |
8 Segment Redundant Fieldbus Power Supply - Vertical DIN Rail |
| |
|
F892-P* |
8 Segment Redundant Fieldbus Power Supply - Horizontal DIN Rail |
| |
8 Segment Simplex Power Supply (includes 1 F801 Power Module (350 mA) and 1 F800-BLK Blanking Module with Carrier) |
| |
|
F890-P*NR |
8 Segment Simplex Fieldbus Power Supply - Vertical DIN Rail |
| |
|
F892-P*NR |
8 Segment Simplex Fieldbus Power Supply - Horizontal DIN Rail |
| |
8 Segment Redundant Power Supply (includes 2 F802 Power Modules (500 mA) with Carrier) |
| |
|
F890-2-P* |
8 Segment Redundant Fieldbus Power Supply - Vertical DIN Rail |
| |
|
F892-2-P* |
8 Segment Redundant Fieldbus Power Supply - Horizontal DIN Rail |
| |
8 Segment Simplex Power Supply (includes 1 F802 Power Module (500 mA) and 1 F800-BLK Blanking Module with Carrier) |
| |
|
F890-2-P*NR |
8 Segment Simplex Fieldbus Power Supply - Vertical DIN Rail |
| |
|
F892-2-P*NR |
8 Segment Simplex Fieldbus Power Supply - Horizontal DIN Rail |
| Pepperl+Fuchs |
| Redundant Fieldbus Power Hub Motherboards >>Additional Info: P+F Application |
| |
MB-FB-4R* 4 Segment |
| |
MB-FB-2R* 2 Segment |
| |
MB-FB-1R* 1 Segment |
|
Simplex Fieldbus Power Hub Motherboards |
| |
MB-FB-4* 4 Segment |
| Power Hub Modules |
| |
HD2-FBPS.1.500 Power Supply, 28-30 Volt |
| |
HD2-FBPS.1.23.500 Power Supply, 21-23 Volt |
| |
HD2-FBPS.1.17.500 Power SupplY, 15-17 Volt |
| |
HD2-DM-B Basic Diagnostic Module |
| Redundant Fieldbus High Density Power Hub Motherboard >>Additional Info: P+F Application |
| |
MBHD-FB-4R* 4 Segment |
| High Density Power Hub Modules |
| |
HD2-FBPS.1.25.360 Power Supply, 25-27 Volt |
| |
HD2-DM-B Basic Diagnostic Module |
| KLD2-STR-1.24.400.IEC ( STR400) (FieldConnex
Branded) Fieldbus Power Supply (Manufactured March,
2004 or later) |
| KLD2-FBPS-1.25.360
Fieldbus Power Supply, 25-27 Volt |
| R.
STAHL Schaltgeraete GmbH |
| Zone 2 or Class I, Div 2 |
| |
9412/PS-I |
Redundant Fieldbus Power Supply with
terminator |
| |
9412/PS-2 |
Redundant Fieldbus Power Supply without terminator |
| |
9412/PS-DT |
Dual (2 segment) Fieldbus Power Supply with terminator |
| |
9412/PS-D |
Dual (2 segment) Fieldbus Power Supply without
terminator |
| MooreHawke |
Routemaster Series 100 With RM114/118 Device Couplers Fieldbus
IS Power Supply
See Knowledge Base Article #NA-0300-0050 |
|
MTL Instruments
|
| MTL5995 Fieldbus Power Supply -- Use MTL5995-PS for New Installations |
| MTL5995-PS Fieldbus Power Supply |
| 9121-IS-PS Fieldbus FISCO IS Power
Supply >>Additional Info: Application
MTL IS |
| 9122-IS-PS Fieldbus FISCO IS Power Supply >>Additional
Info: Application MTL
IS |
| 9111-NI-PS Fieldbus FNICO NI Power
Supply >>Additional Info: Application
MTL NI |
| 9112-NI-PS Fieldbus FNICO NI Power Supply >>Additional
Info: Application MTL
NI |
| 9109-22 Redundant 4 Segment FISCO Power Supply System - Panel Mount (Includes 9109-CA-PS carrier with 9122-IS-CM power modules, 9129-IS supply arbitration modules, and 9126-PU host power modules) |
| F690A-** 4 Segment Redundant Fieldbus
Power Supply with FPS-IPM Power Supplies & FPS-ALM
Alarm Module |
| MTL-Relcom |
| Megablock With and Without SpurGuards™ (Short Circuit Protection) >>Additional Info: Relcom Application |
| Safe Area, Class I Division 2 (Zone 2), or Class I Division 1 (Zone 0,1) |
| |
FCS-MB* |
2, 4, 8, 10, 12 Device Megablock |
| |
FCS-MB*-T |
2, 4, 8, 10, 12 Device Megablock with Fixed Terminator |
| Safe Area, Class I Division 2 and Zone 2 including Energy Limited Spurs |
| |
FCS-MB*-SG |
2, 4, 8, 10, 12 Device Megablock with SpurGuards™ |
| |
FCS-MB*-SG-T |
2, 4, 8, 10, 12 Device Megablock with SpurGuards™ and Fixed Terminator |
| |
F203, F207, F211, F118, F215 |
4, 8, 10, 12 Device Megablock with SpurGuards™ and Switchable Terminator |
| Class I Division 1 and Zone 0,1 - Intrinsically Safe / FISCO |
| |
FCS-MB* |
2, 4, 8, 10, 12 Device Megablock |
| |
FCS-MB*-T |
2, 4, 8, 10, 12 Device Megablock with Fixed Terminator |
| |
F204, F208, F212, F216 |
4, 8, 10, 12 Device Megablock with Switchable Terminator |
| |
F240, F244, F250, F256, F268 |
2, 4, 8, 10, 12 Device IS Megablock |
| |
F242, F246, F252, F258, F270 |
2, 4, 8, 10, 12 Device IS Megablock with Fixed Terminator |
| |
F248, F254, F260, F272 |
4, 8, 10, 12 Device IS Megablock with Switchable Terminator |
| |
F241, F245, F251, F257, F269 |
2, 4, 8, 10, 12 Device IS Megablock with SpurGuards™ |
| |
F243, F247, F253, F259, F271 |
2, 4, 8, 10, 12 Device IS Megablock with SpurGuards™ and Fixed Terminator |
| |
F249, F255, F261, F273 |
4, 8, 10, 12 Device IS Megablock with SpurGuards™ and Switchable Terminator |
| Zone 1 - Increased Safety |
| |
F240-XE, F244-XE, F250-XE, F256-XE, F268-XE |
2, 4, 8, 10, 12 Device IS Megablock |
| |
F242-XE, F246-XE, F252-XE, F258-XE, F270-XE |
2, 4, 8, 10, 12 Device IS Megablock with Fixed Terminator |
| |
F248-XE, F254-XE, F260-XE, F272-XE |
4, 8, 10, 12 Device IS Megablock with Switchable Terminator |
| |
F241-XE, F245-XE, F251-XE, F257-XE, F269-XE |
2, 4, 8, 10, 12 Device IS Megablock with SpurGuards™ |
| |
F243-XE, F247-XE, F253-XE, F259-XE, F271-XE |
2, 4, 8, 10, 12 Device IS Megablock with SpurGuards™ and Fixed Terminator |
| |
F249-XE, F255-XE, F261-XE, F273-XE |
4, 8, 10, 12 Device IS Megablock with SpurGuards™ and Switchable Terminator |
| Turck/InterlinkBT |
| JBBS-49-E413,613,813 |
Eurofast 4,6,8 Device Junction Block (Without Short Circuit Protection) |
| JBBS-49-M413,613,813 |
Minifast 4,6,8 Device Junction Block (Without Short Circuit Protection) |
JBBS-49SC-E413 - U8206-43
JBBS-49SC-E613 - U8206
JBBS-49SC-E813 - U8206-83 |
Eurofast 4,6,8 Device Junction Block With Device
Short Circuit Protection
(Manufactured November, 2004 (4404U) or later |
JBBS-49SC-M413 - U8607
JBBS-49SC-M613 - U7908
JBBS-49SC-M813 - U7909 |
Minifast 4,6,8 Device Junction Block With Device
Short Circuit Protection
(Manufactured November, 2004 (4404U) or later |
| JRBS-49SC-*R |
4,6,8,10,&12 Port Device Coupler with Device Short Circuit Protection, DIN Rail Mount |
| Pepperl+Fuchs |
| Segment Protectors for Zone 2/Class I, Div. 2 applications: >>Additional Info: P+F Application, and P+F NI Application |
 |
F2-JBSC-*.FF.* |
4,6,8 Spur with connectors and Device Short Circuit Protection |
| |
F2-JBSC-* |
4,6,8 Spur with cable glands and Device Short Circuit Protection |
| |
F6-JBSC-*.FF.* |
4,6,8 Spur, Stainless Steel housing with connectors and Device Short Circuit Protection |
| |
F6-JBSC-* |
4,6,8 Spur, Stainless Steel housing with cable glands and Device Short Circuit Protection |
| |
R-JBSC-* |
4,6,8 Spur, DIN-Rail mounting with Device Short Circuit Protection |
| |
(Trunk and Spur Shields (T-S) must be jumpered together and isolated
(remove jumpers) from case ground) |
| |
R-SP-N12 |
12 Spur, DIN-Rail mounting with Device Short Circuit Protection |
| |
R2-SP-N* |
4,6,8,10,12 Spur, DIN-Rail mounting with Device Short Circuit Protection |
| |
Modular Segment Protector |
| |
RM-SPTM-N2 |
Trunk Module with 2 Spurs with Short Circuit Protection |
| |
RM-SPEM-N4 |
Expansion Module 4 Spur with Short Circuit Protection |
| Segment Protectors for Zone 1/Class I, Div. 2 applications: |
| |
R-SP-E12 |
12 Spur, DIN-Rail mounting with Device Short Circuit Protection |
| FieldConnex FISCO/Entity IS FieldBarriers: >>Additional Info: P+F Application |
| |
F2D0-FB-Ex4* |
4 device Barrier with short circuit protection
(Manufactured June, 2003 or later) |
| |
F6D0-FB-Ex4* |
4 device Barrier with Stainless Steel housing and Short Circuit Protection
(Manufactured June, 2003 or later) |
| |
RD0-FB-Ex4* |
4 device Barrier with DIN-Rail mounting and Short Circuit Protection
(Manufactured June, 2003 or later) |
| |
The Field Barrier is Application Dependent – The segment
must be powered by either a Relcom or Pepperl+Fuchs Fieldbus Power
Supply listed above, or an approved Power Conditioner such as a Pepperl+Fuchs
HD2-FBCL.1.500 Power Conditioner module or the KLD2-PC- 1.1.IEC Power
Conditioner . See Knowledge Base Article # NA-0300-0048 |
| R.
STAHL Schaltgeraete GmbH |
| Fieldbus Barriers Ex e/Ex i for Zone 1, 2 or Class I,
Div 2 installation, for Ex i/IS field devices: |
| |
9411/21-2*0-*1 |
4,8 spur barrier with short circuit protection, DIN-rail mount |
| |
9411/21-2*1-*1 |
4,8 spur barrier with short circuit protection, polyester enclosure |
| |
9411/21-2*2-*1 |
4,8 spur barrier with short circuit protection, stainless steel enclosure |
| |
The Field Device Barrier is Application Dependent – The segment must be powered by an approved R. Stahl, Relcom, or Pepperl+Fuchs Fieldbus Power Supply. See Knowledge Base Article # AP-0600-0132 |
| Fieldbus Device Couplers Ex e/Ex e for Zone 1, 2 or Class I, Div 2 installation, for Ex ed/non-IS field devices: |
| |
9411/11-2*0-*0 |
4,8 spur coupler with short circuit protection, DIN-rail mount |
| |
9411/11-2*1-*0 |
4,8 spur coupler with short circuit protection, polyester enclosure |
| |
9411/11-2*2-*0 |
4,8 spur coupler with short circuit protection, stainless steel enclosure |
| |
The Fieldbus Device Coupler must be installed with both trunk and spur shields connected to coupler ground bar as illustrated by Option1 in Knowledge Base Article # AP-0600-0132. |
| Fieldbus Device Couplers non-Ex |
| |
9411/00-010-*0 |
4,8 spur coupler with short circuit protection, DIN-rail mount |
| |
The Fieldbus Device Coupler must be installed with both trunk and spur shields connected to coupler ground bar as illustrated by Option1 in Knowledge Base Article # AP-0600-0132. |
| MTL Instruments |
| Fieldbus Barriers Ex e trunk/Ex i spurs for Zone 1, 2 or Class I, Div 2 installation, for Ex i/IS field devices: |
| |
9311-FB-* |
4 spur barrier with short circuit protection, DIN-rail mount |
| |
9311-FB-*PP |
4 spur barrier with short circuit protection, polyester enclosure |
| |
9311-FB-*SS |
4 spur barrier with short circuit protection, stainless steel enclosure |
| |
The Fieldbus barrier is Application Dependent - The segment must be powered by an approved Relcom, R. Stahl, or Pepperl+Fuchs Fieldbus Power Supply. See Knowledge Base Article # AP-0600-0142 |
| 9321-SC |
Fieldbus IS Entity Spur Adapter (9121-IS Use Only) |
See Application MTL IS |
| 9322-SC |
Fieldbus IS EExia Spur Adapter |
See Application MTL IS |
| 9323-SC |
Fieldbus IS Entity Spur Adapter (9121/22-IS Use Only) |
See Application MTL IS |
| FP32 |
Fieldbus Surge Protector (Rail Mount) |
See Application Note TAN1010 |
| TP32* |
Fieldbus Surge Protector (Threaded) |
See Application Note TAN1010 |
| TP32*-NDI |
Fieldbus IS Surge Protector (Threaded) |
See Application Note TAN1010 |
| Phoenix Contact |
| Fieldbus Device Coupler Zone 2, Class I, Div 2, or Safe Area, FNICO, FISCO ic |
| |
FB -*ET |
Modular Trunk Interface with Terminator |
| |
FB -*SP |
Modular 2,4 Spur Expansion with Short Circuit Protection |
| |
The shield connection switch on the FB-ET Trunk Interface must be in either the default and preferred position 1 (no connect) or alternate position 2 (capacitive coupled). Position 3 (grounded) is NOT supported by Emerson |
| Smar |
| RP302 Fieldbus Repeater |
| MTL Instruments |
| FBT1 |
Fieldbus Terminator |
| FBT1-IS |
Fieldbus IS Terminator |
| Relcom, Inc |
| F100 |
Fieldbus Terminator with Surge Protection |
| FCS-MBT |
Fieldbus IS Terminator with Surge Protection |
| FCS-MBT-XE |
Fieldbus Increased Safety Terminator with Surge Protection |
| Pepperl+Fuchs |
| F*-FT-Ex1.D.IEC |
Fieldbus Terminator (Threaded) |
| F*-FT-Ex1.I.IEC |
Fieldbus IS Terminator (Threaded) |
| R. STAHL Schaltgeraete GmbH |
| Fieldbus Terminators for Zone 1, 2 installation |
| 9418/01-201-10 |
Fieldbus Terminator - Ex e (with leads) |
| 9418/02-201-10 |
Fieldbus IS Terminator - Ex i (with leads) |
| Turck/InterlinkBT |
| RSEV 49 TR |
Eurofast Fieldbus Terminator |
| RSV 49 TR |
Minifast Fieldbus Terminator |
| JRBS-49TR |
Fieldbus Terminator - two pin (For use with JRBS-49SC-*R Coupler) |
back to top
|